PORTABLE OVER | CURRENT RELAYTEST KIT |
(Secondary Injection Kit) | Model: RLY – 108 |
FEATURES: Single Kit with two units
• Two separate inputs & five outputs
• Test outputs available:
Unit – I : 0 to 100 A, AC, 0 to 240 voltsAC
Unit – II: 0 to 2 A AC, 0 to 240 volts AC and aux.
o to 240 volts DC.
• Panel with clear and easy to follow legend.
• Built in TImer for testing relays and circuit breakers.
• Overload protection.
• Independent Digital readouts of current, voltage and time.
• The kit can be used for all types of relays (current and voltage relays
I Low current C.T) except 6 current differential relay & Distance relays
• Weight: 22 kegs. Approx

By using our RelayTest Kit following relays can be tested
Description
• Over current relay
• IDMT over current relay
• Under current
• Earth fault relay
• Over Voltage relay
• Under voltage relay
• Differential relay
• Negative sequence relay
• Synchronizing check relay
• Single Pole circuit Breaker timing
• Checking or interlocking relay
• A.C redosing relay
• Field Failure Relay
• Reverse phase or phase balance current relay
• Bearing protective relay
• Instantaneous over current or rate-of-rise relay
• Circuit breaker auxiliary switch normally closed
• Trip coil supervision relay
• Over nux relay
• Auxiliary relay
• TIme delay stopping or opening relay
(Break failure)
• Blocking relay
• Lock out relay
• Voltage or current balance relay • A.C time over current relay
• Automatic selective control or transfer relay
• Thermal relay
• TIme delay relay
• Circuit breaker auxiliary switch normally open
UNIT – I
• All Types of Electro Magnetic
I Static relays
SUPPLY VOLTAGE 230 Volts, 50 Hz, (± 10%), AC Single Phase supply through Toggle switch & Control Fuse for Units 1 & 2.
OUTPUT 1. Variable current Application 0 – 100AAC
2. For voltage, the Variac output is connected to variable voltage output 0 – 230 V AC with fuse.
3. Separate current output terminals and separate voltage output terminals are provided
(At one time either current or voltage circuit will be connected through a Toggle Switch)
CONTROLS 1. 1st Unit with Push Button Control Only. When the ON/OFF push button is operated, all outputs will be connected to the output connectors
2. 2nd unit with Push Button controt & By-Pass Switch
CURRENT OUTPUT : Output; 0 – 100A- 50A- 25A- 10A – 5A- 1A
Each of these outputs has a separate terminal referred to one common terminal.
Each current output terminal is for 400 VA capacity, except 1A output which is for 250 VA capacity
VOLTAGE OUTPUT RATING
AMMETER
VOLTMETER
PROTECTION TIME INTERVAL
METER
External Timer
: 0·230 V AC 12A – Variable voltage output through fuse units Separate pair of test terminals is provided
Continuous (3min ON 110 Min. OFF)
3 Yo Digit, 12mm LED type. Accuracy: ± 1% (Direct reading 0 – SOA) For current ranges of 1A, SA, lOA,
2SA and SOAAC, readings can be noted direclly from the digital ammeter. Above SOAmps & up to
100Amps readings can be taken through external clamp meter.
3 y, Digit, 12mm LED type. Accuracy:± 1 % (Common meter for measurement of Unit·l & Unit-2 AC
& Unit-2 DC output through a 3 position selector switch)
a. Unit 1 :- Output is 0 -230 V AC. Voltmeter connected through selector switch (Switch Positicn-f )
b. Unit 2 ;·Output is O· 230 V AC. Voltmeter connected through Selector switch. (Switch Positton-z)
c. Unit 2 ;- DC output 0 -2S0 V DC. Volt meter connected through selector Switch (Switch Posiuon-S) Anyone voltage only can be read at a time.
Control Fuse for Mains input and all outputs (current I Voltage)
5 Digit. 12 mm LED. crystal time base.
One five digit timer with toggle selector for NO/NC (for checking the opening and closing time) in mil!i second. The four position timer selection is provided for auto ranges (NO/NC test terminals. reset push button are also provided)
Multi-ranqe: a) 99.999 seconds b) 999.99 seconds c) 9999.9 seconds d) 99999. seconds
The timer will stop on getting the signal from the relay. When the timer stops the current and voltage output is de – energized Separate pair of test terminals (Relay trip contacts) is provided
tor checking breaker opening and closing time
UNIT – 2
SUPPLY VOLTAGE : 230± 10% Volts. 50/60 Hz. AC Single Phase.
SELECTION (MODE)
BY • PASS MODE CONTROL MODE
CURRENT OUTPUT
A.CVOLTAGE OUTPUT
D.CVOLTAGE OUTPUT
RATING PROTECTION CONSTRUCTION DIMENSIONS WEIGHT
: All Outputs are connected through by – pass I control mode switch
: It “By pass” • mode is chosen then all outputs will be directly connected to the output terminals. In this option Timer is in “OFF” mode & “ON I OFF” Push button control is in ‘OFF” position.
: If ‘Push button” control mode is chosen then all outputs will be connected to the output terminals through the “ON/OFF” push button. according to the selection. In this option timer is in ‘ON” mode.
: 0 to 2AAC (Measured by external Clamp meter)
: 0 – 230 V AC With 2A control fuse.
0·250 V DC output through 1.5 A fuse. filtering condenser and bleeder resistor
Continuous
Fuse for Mains Input and all Outputs
Powder coated MS Box with Carrying handle. W x 0 x H: 17.5″ x 13″ x 7.5″ approx.
23 kgs.approx.